Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2018, 10:56 AM
  • G 0085_G 0084_13042018_040555.mp4

Date
04/13/2018
W/O
696290
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00347
PipeID
P10448
Time
3:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5530
Sewer Name
G JOINT OUTFALL G - UNIT 7
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
WO_696290_TV08170_APR2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
G 0085
Downstream MH
G 0084
Dir. of Survey
Downstream
Length Surveyed
17.4 ft.
Total Length
17.4 ft.
Structural Index
4
Structural Quick
5433
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole G 0085 to G 0084
MH: G 0085MH: G 0084downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 00850 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start16.6 ft. HVV - Hole Void Visible, from 11 to 01 o'clock, within 8 inches of joint: YES16.6 ft. SMW - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES - VOID VISIBLE17.4 ft. AMH - Downstream Manhole, Survey Ends - G 008417.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish17.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole Void Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    16.6 ft. - Hole Void Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
17.4AMHG 0084
16.6HVV
0AMHG 0085
0MWM
0MWL
16.6SMWVOID VISIBLE
9.1SRV
17.4SRV
2.1SAP
17.4SAP

Properties (4)

additional_info
SC358737
custom_field_two
1
customer
LACSD
datetime
2018-04-13T03:56:54-07:00