Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 25, 2018, 10:22 AM
  • 15 0882_15 0881 _25042018_033517.mp4

Date
04/25/2018
W/O
695662
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00599
PipeID
P12675
Time
3:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5576
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
WO_695662_TV15182_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0882
Downstream MH
15 0881
Dir. of Survey
Downstream
Length Surveyed
301.8 ft.
Total Length
301.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 15 0882 to 15 0881
MH: 15 0882MH: 15 0881downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08820 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"121 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"182.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"242.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"298.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300 ft. MGO - General Observation - CAPPED CONNECTION INSIDE THE MH. @ 03 O'CLOCK301.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0881

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2SAP
242.6TF
301.8AMH15 0881
0MWM
0AMH15 0882
47.9TFC
182.2TFC
298.5SAP
0MGOCOCKROACHES IN MANHOLE
0MWL
300MGOCAPPED CONNECTION INSIDE THE MH. @ 03 O'CLOCK
121TF

Properties (4)

additional_info
SC358536
custom_field_two
2
customer
LACSD
datetime
2018-04-25T03:22:12-07:00