Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2018, 11:02 AM
  • C 0611_C 0215_5312018_050108.mp4

Date
05/31/2018
W/O
0706820
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09610
Time
4:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0875
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20180531MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0611
Downstream MH
C 0215
Dir. of Survey
Downstream
Length Surveyed
201.8 ft.
Total Length
201.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole C 0611 to C 0215
MH: C 0611MH: C 0215downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 60% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - SLIME COAT FROM HOT SEWAGE START26.6 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT31.2 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE71.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE74.9 ft. MGO - General Observation - 80% MAG COAT START201 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE201 ft. MGO - General Observation - SLIME COAT ON PIPE201 ft. MGO - General Observation - MAHG COAT 80% FINISH201 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active201.8 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (6)

  • General Observation - MAG COAT 60% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 60% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    26.6 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    31.2 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    71.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • General Observation - 80% MAG COAT START

    74.9 ft. - General Observation - 80% MAG COAT START

Observations (15)

DistanceCodeObservation
201SSSBLISTERING PEELING CONCRETE
201.8AMH5:25AM
2MGOMAG COAT 60% START 8:00 TO 4:00
2SSSBLISTERING PEELING CONCRETE
0MWL
74.9MGO80% MAG COAT START
201MGOSLIME COAT ON PIPE
0AMH4:55AM
201MGOMAHG COAT 80% FINISH
0MWM
26.6SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
2MGOSLIME COAT FROM HOT SEWAGE START
31.2SSSPEELING CONCRETE
71.2SSSPEELING CONCRETE
201MGOConn. @ Mh, 9 O' Clock. Active

Properties (4)

custom_field_three
BLISTERING PEELING CONCRETE-80% MAG COAT
custom_field_two
3
customer
LACSD
datetime