Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2018, 07:40 AM
  • A 0394_A 0393_5292018_004543.mp4

Date
05/29/2018
W/O
0706830
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08304
Time
12:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0872
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180525MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
A 0394
Downstream MH
A 0393
Dir. of Survey
Downstream
Length Surveyed
668.7 ft.
Total Length
668.7 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
23
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
28
Pipe schematic from manhole A 0394 to A 0393
MH: A 0394MH: A 0393downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 50% START 8:00 TO 4:0026.5 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR34.9 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, - SEVERE AGG91.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG124 ft. MGO - General Observation - MAG COAT 80% START531.2 ft. SAV - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG602.2 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR639.5 ft. MWLS - Water Level, Sag in pipe, 60 %of cross sectional area, Start639.5 ft. MWL - Water Level, 70 %of cross sectional area639.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEEPLING CONCRETE639.5 ft. MWM - Water Mark, 90 %of cross sectional area639.5 ft. SAV - Surface Aggregate VISIBLE from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG639.5 ft. MGO - General Observation - MAG COAT 80-% FINISH661.7 ft. MWLS - Water Level, Sag in pipe, 60 %of cross sectional area, Finish661.7 ft. MWL - Water Level, 20 %of cross sectional area661.7 ft. MWM - Water Mark, 30 %of cross sectional area668.7 ft. AMH - Downstream Manhole, Survey Ends - 1:45AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 50% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 50% START 8:00 TO 4:00

  • Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    26.5 ft. - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES,  - SEVERE AGG

    34.9 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    91.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

  • General Observation - MAG COAT 80% START

    124 ft. - General Observation - MAG COAT 80% START

  • Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    531.2 ft. - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    602.2 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Water Mark, 90 %of cross sectional area

    639.5 ft. - Water Mark, 90 %of cross sectional area

Observations (21)

DistanceCodeObservation
34.9SAMSEVERE AGG
639.5MWLS
0AMH12:45AM
0MWM
661.7MWLS
639.5MWL
124MGOMAG COAT 80% START
639.5SSSBLISTERING PEEPLING CONCRETE
91.5SAVSEVERE AGG
639.5MWM
602.2SRVCIRCUM REBAR
661.7MWL
531.2SAVSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
668.7AMH1:45AM
639.5SAVSEVERE AGG
26.5FCCIRCUM REBAR
661.7MWM
0MWL
639.5MGOMAG COAT 80-% FINISH
2MGOMAG COAT 50% START 8:00 TO 4:00

Properties (4)

custom_field_three
CIRCUM REBAR VISIBLE- 80% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2018-05-29T00:40:06-07:00