Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2018, 11:11 AM
  • A 0395_A 0394_5252018_042352.mp4

Date
05/25/2018
W/O
0706830
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08305
Time
4:11 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0871
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180525MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0395
Downstream MH
A 0394
Dir. of Survey
Downstream
Length Surveyed
520.9 ft.
Total Length
520.9 ft.
Structural Index
4
Structural Quick
5642
Structural Rating
46
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
46
Pipe schematic from manhole A 0395 to A 0394
MH: A 0395MH: A 0394downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM2 ft. MGO - General Observation - MAG COAT 60% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE14.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT14.8 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT42 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG115.3 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG118.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR134.9 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG149 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR149.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR186.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRUN REBAR502.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - REBAR UNDER MAG COAT520.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR UNDER MAG COAT520.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE520.3 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT520.9 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (12)

  • General Observation - MAG COAT 60% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 60% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR  UNDER MAG COAT

    14.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    14.8 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    42 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    115.3 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    118.2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    134.9 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    149 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    149.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRUN REBAR

    186.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRUN REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - REBAR UNDER MAG COAT

    502.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - REBAR UNDER MAG COAT

Observations (19)

DistanceCodeObservation
42SAVSEVERE AGG
149SRVCIRCUM REBAR
520.3SRVCIRCUM REBAR UNDER MAG COAT
118.2SRVCIRCUM REBAR
520.9AMH5:30AM
2MGOMAG COAT 60% START 8:00 TO 4:00
520.3SSSBLISTERING PEELING CONCRETE
134.9SAMSEVERE AGG
0MWM
149.3SRVCIRCUM REBAR
186.7SRVCIRUN REBAR
2SSSPEELING BLISTERING CONCRETE
14.8SRVCIRCUM REBAR UNDER MAG COAT
502.9SRVREBAR UNDER MAG COAT
0MWL
14.8SAMSEVERE AGG UNDER MAG COAT
520.3SAMSEVERE AGG UNDER MAG COAT
0AMH4:35AM
115.3SAVSEVERE AGG

Properties (4)

custom_field_three
CIRCUM REBAR UNDER MAG COAT
custom_field_two
2
customer
LACSD
datetime
2018-05-25T04:11:33-07:00