Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2018, 06:53 AM
  • 15 0410_15 0409 _04052018_002119.mp4

Date
05/03/2018
W/O
695786
Weather
Dry
Operator/Surveyor
S . LOPEZ
Sewer ID
Z00607
PipeID
P12333
Time
11:53 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5585
Sewer Name
15 HILL DRIVE EXTENSION TRUNK
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_695786_TV15033_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 0410
Downstream MH
15 0409
Dir. of Survey
Downstream
Length Surveyed
188 ft.
Total Length
188 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2311
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0410 to 15 0409
MH: 15 0410MH: 15 0409downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 04100 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. MLC - Lining Change, Cured in place7.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"49.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"72.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 11 o'clock, , within 8 inches of joint: NO73.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"74 ft. RFL - Roots Fine Lateral, at 01 o'clock74.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"92.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"151 ft. MGO - General Observation - POSSIBLE SEALED CONNECTION @ 10 O'CLOCK188 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish188 ft. MGO - General Observation - COCKROACHES IN MANHOLE188 ft. AMH - Downstream Manhole, Survey Ends - 15 0409188 ft. MGO - General Observation - ACTIVE CONNECTION 10 O' CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 12 to 11 o'clock,  , within 8 inches of joint: NO

    72.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 11 o'clock, , within 8 inches of joint: NO

Observations (17)

DistanceCodeObservation
7.4TFA
188DAGS
73.2TFA
188MGOCOCKROACHES IN MANHOLE
92.4TFA
0AMH15 0410
188AMH15 0409
74.6TFA
151MGOPOSSIBLE SEALED CONNECTION @ 10 O'CLOCK
2MLC
188MGOACTIVE CONNECTION 10 O' CLOCK
0DAGS
72.8DAGS
0MWL
0MWM
74RFL
49.6TFA

Properties (5)

additional_info
SC358549
custom_field_two
3
customer
LACSD
datetime
2018-05-03T23:53:11-07:00
year_laid
39203