Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2018, 06:46 PM
  • 08 0135_08 0134_5232018_122528.mp4

Date
05/23/2018
W/O
0706725
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00006
PipeID
P00191
Time
11:46 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7718
Sewer Name
08 FIGUEROA STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20180523DF_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0134
Downstream MH
08 0135
Dir. of Survey
Upstream
Length Surveyed
383.1 ft.
Total Length
383.1 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole 08 0134 to 08 0135
MH: 08 0134MH: 08 0135upstream0 ft. MGO - General Observation - Grease Throughout The Reach (5%)0 ft. AMH - Upstream Manhole, Survey Ends - 1:06 PM2.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.4 ft. MGP - General Photograph32.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"83.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open117.4 ft. MGP - General Photograph135 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"186.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"236.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"262.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish272.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start272.8 ft. MGP - General Photograph275.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES287.4 ft. MGP - General Photograph310.7 ft. MGP - General Photograph316.2 ft. MGP - General Photograph317.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start319.9 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES319.9 ft. MGP - General Photograph323.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES327.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start357 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES381.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start383 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. UNKNOWN383 ft. MWM - Water Mark, 20 %of cross sectional area383 ft. MWL - Water Level, 15 %of cross sectional area383.1 ft. AMH - Downstream Manhole, Survey Begins - 11:52 AM

Observation photos (15)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    26.1 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    55.4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    59.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    63.2 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • General Photograph

    63.2 ft. - General Photograph

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    65.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    66.9 ft. - General Photograph

  • General Photograph

    72.4 ft. - General Photograph

  • General Photograph

    95.7 ft. - General Photograph

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    107.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    110.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph

    110.3 ft. - General Photograph

  • General Photograph

    265.7 ft. - General Photograph

  • General Photograph

    375.7 ft. - General Photograph

Observations (30)

DistanceCodeObservation
248.1TFC
265.7MGP
65.6CM
110.3DAGS
66.9MGP
2SSS
0.1MGOConn. @ Mh, 9 O' Clock. UNKNOWN
110.3MGP
146.7TFC
380.7RFJ
380.7SSS
383.1MGOGrease Throughout The Reach (5%)
72.4MGP
299.3TFOpen
26.1CM
55.4RFJ
375.7MGP
383.1AMH1:06 PM
120.6DAGS
0AMH11:52 AM
95.7MGP
0.1MWM
380.7CM
107.9DAGS
63.2CM
0.1MWL
196.9TFC
63.2MGP
350.3TFC
59.5CL

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-05-23T11:46:14-07:00