Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2017, 08:52 PM
Date
03/23/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00279
PipeID
P21004
Time
1:52 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4323
Sewer Name
02 MONTEBELLO TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_624375_TV02084_MAR20172
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 2375
Downstream MH
02 2374
Dir. of Survey
Downstream
Length Surveyed
262.4 ft.
Total Length
262.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2T00
O&M Rating
208
Overall Index
2
Overall Quick
Overall Rating
208
Pipe schematic from manhole 02 2375 to 02 2374
MH: 02 2375MH: 02 2374downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 23753 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start60 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4"90.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"164.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4"168 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"243 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"262.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish262.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish262.4 ft. AMH - Downstream Manhole, Survey Ends - 02 2374

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
164.1TF
3DAE
0MWL
90.1TFA
0MWM
262.4AMH02 2374
0AMH02 2375
3DAGS
168TFA
262.1DAE
60TF
243TFA
262.1DAGS

Properties (4)

additional_info
SC318738
custom_field_two
4
customer
LACSD
datetime