Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2016, 05:49 AM
  • 02 2350_02 2349_20161018_230015.mp4

Date
10/18/2016
W/O
597387
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00290
PipeID
P20981
Time
10:49 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3743
Sewer Name
02 MONTEREY PARK EXTENSION RELIEF TRUNK
City
MONTEREY PARK, CA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_597387_TV02101_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 2350
Downstream MH
02 2349
Dir. of Survey
Downstream
Length Surveyed
300.1 ft.
Total Length
300.1 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
122
Pipe schematic from manhole 02 2350 to 02 2349
MH: 02 2350MH: 02 2349downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 23502.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start102.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"132.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"240.3 ft. CH2 - Crack Longitudinal Hinge, 2, from 08 to 10 o'clock, within 8 inches of joint: YES296.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish300.1 ft. AMH - Downstream Manhole, Survey Ends - 02 2349

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal Hinge, 2, from 08 to 10 o'clock, within 8 inches of joint: YES

    240.3 ft. - Crack Longitudinal Hinge, 2, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
132.5TB
0MWL
0MWM
296.9DAGS
2.5DAGS
240.3CH2
300.1AMH02 2349
0AMH02 2350
102.9TF

Properties (5)

additional_info
SC303732
custom_field_two
3
customer
LACSD
datetime
2016-10-18T22:49:00-07:00
year_laid
33533