Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2016, 10:39 AM
  • 02 0765_02 0764_20160718_045432.mp4

Date
07/18/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03323
Time
3:39 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3656
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0764
Downstream MH
02 0765
Dir. of Survey
Upstream
Length Surveyed
312.7 ft.
Total Length
312.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 0764 to 02 0765
MH: 02 0764MH: 02 0765upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 07652.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish41.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"93.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"144.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"186.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"244.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"293.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"310.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start312.7 ft. MWM - Water Mark, 25 %of cross sectional area312.7 ft. AMH - Downstream Manhole, Survey Begins - 02 0764312.7 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (5)

  • Water Mark, 25 %of cross sectional area

    0 ft. - Water Mark, 25 %of cross sectional area

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"

    168 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"

    219.6 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    310.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (12)

DistanceCodeObservation
168TFC
310.5DAGS
125.9TFC
312.7AMH02 0765
219.6TFC
0MWM
2DAGS
68.4TFC
0AMH02 0764
19.6TFC
270.8TFC
0MWL

Properties (4)

additional_info
SC305535
custom_field_two
4
customer
LACSD
datetime
2016-07-18T03:39:52-07:00