Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2016, 10:41 AM
Date
07/20/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03354
Time
3:41 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3658
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0790
Downstream MH
02 0789
Dir. of Survey
Downstream
Length Surveyed
340.8 ft.
Total Length
340.8 ft.
Structural Index
3
Structural Quick
3323
Structural Rating
15
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
19
Pipe schematic from manhole 02 0790 to 02 0789
MH: 02 0790MH: 02 0789downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES22.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES33 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"35.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"45.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES65 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES84.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"87.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"128.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES136.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"139.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"188.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"191.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"237 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"240.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"291.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"294.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"321.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES327.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"327.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"334.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish338.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish340.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0789

Observation photos (6)

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    45.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    65 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    191.1 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    327.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    334.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (28)

DistanceCodeObservation
191.1TFA
45.7CM
3.4DAGS
334.9CM
35.9TFC
0AMH02 0790
139.5CM
136.5TFC
338.1DAGS
84.3TFC
321.2DAGS
327.9TFC
0MWM
188.1TFC
340.8AMH02 0789
33TFC
65CL
13CL
128.5CM
294.8TFA
291.2TFC
22.6CL
240.1TFC
0MWL
237TFC
327.8TFC
139.5TFC
87.6TFC

Properties (4)

additional_info
SC305537
custom_field_two
3
customer
LACSD
datetime