Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2016, 09:37 AM
Date
07/19/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03303
Time
2:37 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3657
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0746
Downstream MH
02 0748
Dir. of Survey
Upstream
Length Surveyed
285.5 ft.
Total Length
285.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 0746 to 02 0748
MH: 02 0746MH: 02 0748upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Ends - 02 07483.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish32.3 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES70.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"73.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"170.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"172.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"270.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"272.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"283.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start285.5 ft. AMH - Downstream Manhole, Survey Begins - 02 0746285.5 ft. MWM - Water Mark, 10 %of cross sectional area285.5 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    212.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"

  • Deposits Attached Ragging, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    253.2 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Finish

    282 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observations (14)

DistanceCodeObservation
0AMH02 0746
112.6TFA
212.3TFC
2DAGS
285.5MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
285.5AMH02 0748
115TFC
0MWM
214.7TFC
0MWL
282DAGS
13.3TFC
253.2DAR
14.7TFC

Properties (4)

additional_info
SC305536
custom_field_two
4
customer
LACSD
datetime
2016-07-19T02:37:00-07:00