Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2016, 11:36 AM
Date
07/18/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03317
Time
4:36 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3656
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
V
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0758
Downstream MH
02 0759
Dir. of Survey
Upstream
Length Surveyed
231 ft.
Total Length
231 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 0758 to 02 0759
MH: 02 0758MH: 02 0759upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - REVERASL INSPECTION COMPLETE AT ROOT MASS48 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"51.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"62.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES96.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"99.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"130 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES137 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES142.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"145.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"152 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES198.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"201.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"229 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start231 ft. MWL - Water Level, 5 %of cross sectional area231 ft. MWM - Water Mark, 20 %of cross sectional area231 ft. AMH - Downstream Manhole, Survey Begins - 02 0758

Observation photos (7)

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    29.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    79 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    94 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    101 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
85.1TFA
179.8TFC
0MWL
32.9TFC
88.2TFA
134.4TFC
231DAGS
2DAGS
231MSAREVERASL INSPECTION COMPLETE AT ROOT MASS
183TFC
94CL
168.6CL
0MWM
131.4TFC
79CM
0AMH02 0758
29.9TFC
101CL

Properties (4)

additional_info
SC305535
custom_field_two
4
customer
LACSD
datetime