Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2016, 09:15 AM
Date
07/19/2016
W/O
574316
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00294
PipeID
P03302
Time
2:15 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3657
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_574316_TV02111_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0745
Downstream MH
02 0746
Dir. of Survey
Upstream
Length Surveyed
298.8 ft.
Total Length
298.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0745 to 02 0746
MH: 02 0745MH: 02 0746upstream0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Ends - 02 07463.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish83.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"83.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"149.4 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 3"191.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"193.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"223.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"290.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"294 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"296.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start298.8 ft. MWM - Water Mark, 10 %of cross sectional area298.8 ft. AMH - Downstream Manhole, Survey Begins - 02 0745298.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (6)

  • Water Mark, 10 %of cross sectional area

    0 ft. - Water Mark, 10 %of cross sectional area

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    4.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    74.9 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    107.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 3"

    149.4 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 3"

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Finish

    295.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observations (15)

DistanceCodeObservation
7.9TFC
298.8VC
295.6DAGS
149.4TBA
215TFC
0MWM
0AMH02 0745
298.8AMH02 0746
0MWL
107.5TFA
4.8TFC
2DAGS
74.9TFA
105.3TFC
215.2TFC

Properties (4)

additional_info
SC305536
custom_field_two
4
customer
LACSD
datetime
2016-07-19T02:15:00-07:00