Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2018, 01:45 PM
  • Section#6_18 0895_18 0894__4282018__G6991.mp4

Date
04/28/2018
W/O
0701634
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14746
Time
6:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
G6991
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SOUTH WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
20180428MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
18 0895
Downstream MH
18 0894
Dir. of Survey
Downstream
Length Surveyed
489.6 ft.
Total Length
489.6 ft.
Structural Index
2
Structural Quick
2S00
Structural Rating
200
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 18 0895 to 18 0894
MH: 18 0895MH: 18 0894downstream0 ft. AMH - Upstream Manhole, Survey Begins - 7:30AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - 98% MAG COAT START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT255.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRERE278.1 ft. MGO - General Observation - 100% MAG COAT363.3 ft. SSS - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE451.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE489.2 ft. MGO - General Observation - 98% MAG COAT FINISH489.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE489.6 ft. AMH - Downstream Manhole, Survey Ends - 8:00AM

Observation photos (6)

  • General Observation - 98% MAG COAT START 8:00 TO 4:00

    2 ft. - General Observation - 98% MAG COAT START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRERE

    255.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRERE

  • General Observation - 100% MAG COAT

    278.1 ft. - General Observation - 100% MAG COAT

  • Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    363.3 ft. - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    451.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

Observations (12)

DistanceCodeObservation
0AMH7:30AM
0MWM
2MGO98% MAG COAT START 8:00 TO 4:00
451.5SSSBLISTERING CONCRETE
363.3SSSPEELING CONCRETE
255.3SSSBLISTERING CONCRERE
489.2MGO98% MAG COAT FINISH
489.2SSSBLISTERING PEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWL
278.1MGO100% MAG COAT
489.6AMH8:00AM

Properties (4)

custom_field_three
VERY SPORATIC SEVERE AGG-98% MAG COAT
custom_field_two
4
customer
LACSD
datetime
2018-04-28T06:45:00-07:00