Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2018, 11:29 AM
  • 15 1049_15 1048 _30042018_044515.mp4

Date
04/30/2018
W/O
696292
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00631
PipeID
P12808
Time
4:29 AM
Certificate
U-111-1180
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5580
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_696292_TV15031_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1049
Downstream MH
15 1048
Dir. of Survey
Downstream
Length Surveyed
254.3 ft.
Total Length
254.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
102
Pipe schematic from manhole 15 1049 to 15 1048
MH: 15 1049MH: 15 1048downstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. AMH - Upstream Manhole, Survey Begins - 15 10490 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area35.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"84.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"136.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"185 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"194.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"233.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"254.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish254.3 ft. MGO - General Observation - ACTIVE CONNECTION IN MH 3 O'CLOCK254.3 ft. AMH - Downstream Manhole, Survey Ends - 15 1048

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
254.3DAGS
254.3MGOACTIVE CONNECTION IN MH 3 O'CLOCK
84.5TFA
194.1TFA
233.5TFA
35.5TFA
0DAGS
136.1TFA
0AMH15 1049
254.3AMH15 1048
0MWL
185TFC
0MWM

Properties (4)

additional_info
SC358540
custom_field_two
3
customer
LACSD
datetime