Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2018, 05:00 AM
  • 01 1176A_01 1176_02052018_221515.mp4

Date
05/02/2018
W/O
695981
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02029
Time
10:00 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5553
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_695981_TV01257_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1176A
Downstream MH
01 1176
Dir. of Survey
Downstream
Length Surveyed
193.8 ft.
Total Length
193.8 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
149
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
151
Pipe schematic from manhole 01 1176A to 01 1176
MH: 01 1176AMH: 01 1176downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 1176A0.2 ft. MWM - Water Mark, 30 %of cross sectional area3.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES6.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"50 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish67.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES182.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES183.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"193.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish193.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1176193.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    3.9 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    180.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    182.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
3.9SAV
193.8SAV
67.8TF
0MGOCONNECTION AT MH 3 O'CLOCK
3.9CM
42TF
0MWL
96.5TFA
142.5TF
145.3TF
6.3CM
104.3TF
193.8AMH01 1176
182.2CL
193.8MGOCONNECTION AT MH 3 O'CLOCK
0.2MWM
57.7CM
0AMH01 1176A
50TF
183.9TFA
180.7DAGS

Properties (4)

additional_info
SC359308
custom_field_two
3
customer
LACSD
datetime
2018-05-02T22:00:24-07:00