Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2018, 07:37 AM
  • 02 0994_02 0993_04052018_005046.mp4

Date
05/04/2018
W/O
695978
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00279
PipeID
P03566
Time
12:37 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5609
Sewer Name
02 MONTEBELLO TRUNK
City
COMMERCE, CA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
WO_695978_TV02334_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0994
Downstream MH
02 0993
Dir. of Survey
Downstream
Length Surveyed
170.6 ft.
Total Length
170.6 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 0994 to 02 0993
MH: 02 0994MH: 02 0993downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 09940 ft. MWL - Water Level, 20 %of cross sectional area10.1 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES17.8 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES30.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES39 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start105.3 ft. RPR - Repair Pipe Replaced, within 8 inches of joint: YES, Start - VCP110.7 ft. RPR - Repair Pipe Replaced, within 8 inches of joint: YES, Finish - VCP164 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"170.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0993170.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    10.1 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    17.8 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    30.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    39 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Pipe Replaced, within 8 inches of joint: YES, Start - VCP

    105.3 ft. - Repair Pipe Replaced, within 8 inches of joint: YES, Start - VCP

Observations (12)

DistanceCodeObservation
30.9FM
164TB
39CM
10.1CC
105.3RPRVCP
0MWM
17.8CM
0AMH02 0994
0MWL
170.6AMH02 0993
110.7RPRVCP
170.6CM

Properties (4)

additional_info
SC359161
custom_field_two
3
customer
LACSD
datetime
2018-05-04T00:37:13-07:00