Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2018, 07:37 AM
  • E 0209_01 0053A_03052018_004516.mp4

Date
05/03/2018
W/O
695951
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P02146
Time
12:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5554
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_695951_TV01254_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0053A
Downstream MH
E 0209
Dir. of Survey
Upstream
Length Surveyed
160.9 ft.
Total Length
160.9 ft.
Structural Index
4
Structural Quick
4E00
Structural Rating
124
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
4
Overall Quick
Overall Rating
136
Pipe schematic from manhole 01 0053A to E 0209
MH: 01 0053AMH: E 0209upstream0 ft. AMH - Upstream Manhole, Survey Ends - E 02090 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish92.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish143.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start154 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start160.9 ft. MWL - Water Level, 5 %of cross sectional area160.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK160.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK160.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0053A160.9 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (2)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    6.9 ft. - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
14.6TFC
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
0MGOCONNECTION AT MH 9 O'CLOCK
6.9FM
6.9DSF
68.3TFC
160.9AMHE 0209
160.9FM
0AMH01 0053A
17.2TFC
37.9DSF
67.6TFC
0MWM

Properties (4)

additional_info
SC359309
custom_field_two
2
customer
LACSD
datetime
2018-05-03T00:37:00-07:00