Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2018, 12:10 PM
  • 08 0137_08 0136_5162018_051346.mp4

Date
05/16/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00193
Time
5:10 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0857
Sewer Name
08 FIGUEROA STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Capital Improvement Program Assesment
Project
20180516MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
08 0137
Downstream MH
08 0136
Dir. of Survey
Downstream
Length Surveyed
340 ft.
Total Length
340 ft.
Structural Index
2
Structural Quick
3429
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
30
Pipe schematic from manhole 08 0137 to 08 0136
MH: 08 0137MH: 08 0136downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM8 ft. MGO - General Observation - 10" VCP15.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped15.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHR17.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL25.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL61.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H62.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped113.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped115.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H115.1 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL164.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped190.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H210.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H210.4 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL274.8 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL279.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL295.2 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL327.5 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL339.8 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped340 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (1)

  • General Observation - 10" VCP

    8 ft. - General Observation - 10" VCP

Observations (23)

DistanceCodeObservation
190.1FLH
210.4FCH
0MWM
62.6TFCCapped
274.8FCSL
327.5FCSL
17.5FCSL
339.8MGOConn. @ Mh, 3 O' Clock. Capped
15.3TFCCapped
113.7TFCCapped
115.1FCH
340AMH5:40AM
61.5FLH
0MWL
115.1FCSL
8MGO10" VCP
25.2FLSL
15.3FLSLIGHR
164.6TFCCapped
210.4FCSL
295.2FCSL
279.2FCSL
0AMH5:15AM

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-05-16T05:10:43-07:00