Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2018, 07:55 AM
  • 01 0976_01 0975_5142018_023236.mp4

Date
05/14/2018
W/O
0705547
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01814
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0854 & H0855
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
20180511MDM_WRIGHT_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
01 0976
Downstream MH
01 0975
Dir. of Survey
Downstream
Length Surveyed
328.9 ft.
Total Length
328.9 ft.
Structural Index
2
Structural Quick
3C2D
Structural Rating
111
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 01 0976 to 01 0975
MH: 01 0976MH: 01 0975downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:15AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area1.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLUIGHT1.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - SLIGHT12.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL15.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE15.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL17.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H23.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT28.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H38.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL41.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H43.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H43.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H57.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H62.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H76.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H79.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H81.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H84.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H86.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H106.1 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL107.5 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL107.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H110.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL110.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL121.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H133.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H141.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H152 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H154.6 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - H159.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H169.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H169.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H172 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES179.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H185.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL189.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H205.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H215.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL222.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL231.5 ft. MGO - General Observation - LINK PIPE BENT AND NOT IN PLACE TABS233.9 ft. MLC - Lining Change, Other (enter details in Field 39) - LINER START242.3 ft. MGO - General Observation - ON DVD H0855242.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL242.3 ft. MLC - Lining Change, Other (enter details in Field 39) - END LINER245.9 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - ROCKS254.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT269.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H279.4 ft. B - Broken, from 12 to 01 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE300.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL306.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H316 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL317.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL326.6 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H326.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL328.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active328.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active328.9 ft. AMH - Downstream Manhole, Survey Ends - 3:15AM

Observation photos (11)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES,  - SLIGHT

    2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

    23.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    121.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    141.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    185.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • General Observation - LINK PIPE BENT AND NOT IN PLACE TABS

    231.5 ft. - General Observation - LINK PIPE BENT AND NOT IN PLACE TABS

  • Lining Change, Other (enter details in Field 39) - LINER START

    233.9 ft. - Lining Change, Other (enter details in Field 39) - LINER START

  • Lining Change, Other (enter details in Field 39) - END LINER

    242.3 ft. - Lining Change, Other (enter details in Field 39) - END LINER

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - ROCKS

    245.9 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - ROCKS

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    254.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Broken, from 12 to 01 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE

    279.4 ft. - Broken, from 12 to 01 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE

Observations (63)

DistanceCodeObservation
76.6FLH
254.6FLSLIGHT
242.3MGOON DVD H0855
1.5FLSLUIGHT
215.9FCSL
169.9FCH
43.9FLH
245.9DSZROCKS
300.8FCSL
86.5FCH
81.7FLH
28.3FLH
15.2FLHAIRLINE
121.1FLH
179.6FCH
172FC
328.6MGOConn. @ Mh, 9 O' Clock. Active
316FCSL
328.6MGOConn. @ Mh, 3 O' Clock. Active
1.5FLSL
185.1FLSL
328.9AMH3:15AM
43.9FCH
0MWM
57.6FLH
189.5FCH
233.9MLCLINER START
0AMH2:15AM
141.6FLH
17.7FLH
0MGOConn. @ Mh, 9 O' Clock. Active
154.6FCH
169.8FLH
62.1FCH
110.8FCSL
107.5FCSL
12.8FLSL
0MGOConn. @ Mh, 3 O' Clock. Active
79.6FLH
110.8FLSL
222.8FCSL
317.7FCSL
231.5MGOLINK PIPE BENT AND NOT IN PLACE TABS
106.1FCSL
306.2FLH
242.3FLSL
269.4FCH
84.4FCH
107.5FCH
326.6FCH
41.4FCH
326.6FLSL
133.7FLH
205.6FLH
279.4BSLIGHT FRACTURE
242.3MLCEND LINER
23.9FLSLIGHT
0MWL
152FLH
159.9FCH
2FLSLIGHT
38.7FCSL
15.2FCSL

Properties (4)

custom_field_three
BROKEN PIPE SLIGHT FRACTURE-DAMAGED LINK PIPE
custom_field_two
2
customer
LACSD
datetime
2018-05-14T00:55:58-07:00