Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 24, 2016, 10:13 AM
  • 32 0083_32 0082_24052016_031351.mp4

Date
05/24/2016
W/O
574354
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00889
PipeID
P19846
Time
3:13 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3508
Sewer Name
32 RYE CANYON TRUNK
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
04
Purpose
Routine Assessment
Project
WO_574354_TV32020_JUNE2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
32 0083
Downstream MH
32 0082
Dir. of Survey
Downstream
Length Surveyed
502.3 ft.
Total Length
502.3 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2S00
O&M Rating
202
Overall Index
2
Overall Quick
Overall Rating
212
Pipe schematic from manhole 32 0083 to 32 0082
MH: 32 0083MH: 32 0082downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 00832 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES20.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"98.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES210.1 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES272.4 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"494.2 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES498.1 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES501 ft. MGO - General Observation - COCKROACHES IN MANHOLE501 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish502.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0082

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    5 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    210.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 07 to 11 o'clock,  , within 8 inches of joint: YES

    210.1 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 07 to 11 o'clock, , within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    494.2 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    498.1 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    501 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
498.1CM
502.3AMH32 0082
0MWL
2DAGS
501MGOCOCKROACHES IN MANHOLE
0MWM
272.4TBA
501DAGS
0AMH32 0083
20.5TFA
98.7TBA
210.1CL
210.1DAE
5FS
494.2CS

Properties (4)

additional_info
SC305638
custom_field_two
3
customer
LACSD
datetime
2016-05-24T03:13:47-07:00