Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2018, 05:59 AM
  • 29 0193_29 0173 _29012018_221618.mp4

Date
01/29/2018
W/O
684976
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01025
PipeID
P24091
Time
9:59 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5426
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_684976_TV29048_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0193
Downstream MH
29 0173
Dir. of Survey
Downstream
Length Surveyed
326.3 ft.
Total Length
326.3 ft.
Structural Index
3
Structural Quick
5241
Structural Rating
83
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
83
Pipe schematic from manhole 29 0193 to 29 0173
MH: 29 0193MH: 29 0173downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 01930 ft. MWL - Water Level, 5 %of cross sectional area0 ft. B - Broken, from 03 to 09 o'clock, within 8 inches of joint: YES0 ft. MWM - Water Mark, 5 %of cross sectional area2 ft. MGO - General Observation - SPALLING FROM 8 TO 4 O'CLOCK @ 2' MARK TO 325'6.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES9.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"43 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"215 ft. B - Broken, from 03 to 09 o'clock, within 8 inches of joint: YES, Start215 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish215 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES, Start217.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"219 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start219 ft. B - Broken, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish219 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES, Finish239 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"326.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK326.3 ft. AMH - Downstream Manhole, Survey Ends - 29 0173

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES, Start

    215 ft. - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    219 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (30)

DistanceCodeObservation
219CM
188.4TF
0AMH29 0193
0MWL
215B
93.5TFC
215CM
2MGOSPALLING FROM 8 TO 4 O'CLOCK @ 2' MARK TO 325'
51.7TB
0B
289TFC
0MWM
9.4CM
144TFC
40.6TFC
326.2CM
217.6TB
141.7TFC
326.2MGOCONNECTION AT MH 9 O'CLOCK
215FM
190.9TFC
43TFC
241.1TFC
91.1TFC
6.1CM
239TFC
219B
326.3AMH29 0173
219FM
292.1TF

Properties (4)

additional_info
SC347061
custom_field_two
1
customer
LACSD
datetime
2018-01-29T21:59:42-08:00