Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2016, 07:43 AM
  • 01 0690_01 0689_03102016_012415.mp4

Date
10/03/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01399
Time
12:43 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3597
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0690
Downstream MH
01 0689
Dir. of Survey
Downstream
Length Surveyed
420.6 ft.
Total Length
420.6 ft.
Structural Index
3
Structural Quick
513P
Structural Rating
266
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
266
Pipe schematic from manhole 01 0690 to 01 0689
MH: 01 0690MH: 01 0689downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06902.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2.1 ft. MGO - General Observation - MAG COAT 50%27.3 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO27.3 ft. SAP - Surface Aggregate Projecting, from 01 to 03 o'clock, within 8 inches of joint: NO36 ft. SAP - Surface Aggregate Projecting, from 01 to 04 o'clock, within 8 inches of joint: NO339.1 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES392.1 ft. SAP - Surface Aggregate Projecting, at 09 o'clock, within 8 inches of joint: NO418.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish420.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0689

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    27.3 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 01 to 03 o'clock, within 8 inches of joint: NO

    27.3 ft. - Surface Aggregate Projecting, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 01 to 04 o'clock, within 8 inches of joint: NO

    36 ft. - Surface Aggregate Projecting, from 01 to 04 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES

    339.1 ft. - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, at 09 o'clock, within 8 inches of joint: NO

    392.1 ft. - Surface Aggregate Projecting, at 09 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
339.1SAP
27.3SRV
27.3SAP
392.1SAP
418.1SAV
420.6AMH01 0689
0MWL
2.1SAV
0MWM
0AMH01 0690
36SAP
2.1MGOMAG COAT 50%

Properties (4)

additional_info
SC306192
custom_field_two
3
customer
LACSD
datetime
2016-10-03T00:43:42-07:00