Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2018, 04:36 PM
  • Section#1_C 0121_C 0120__542018__G6997.mp4

Date
05/04/2018
W/O
0694536
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00127
PipeID
P09644
Time
9:36 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6997
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Routine Assessment
Project
20180504SHO_JOINT_OUTFALL_C_UNIT_4B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
C 0121
Downstream MH
C 0120
Dir. of Survey
Downstream
Length Surveyed
774.6 ft.
Total Length
774.6 ft.
Structural Index
3
Structural Quick
3^00
Structural Rating
459
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
459
Pipe schematic from manhole C 0121 to C 0120
MH: C 0121MH: C 0120downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 09458 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. MGO - General Observation - 40% MAG COAT INTACT774.6 ft. AMH - Downstream Manhole, Survey Ends - 1115774.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
8SAP
0MWM
774.6AMH1115
0AMH0945
8MGO40% MAG COAT INTACT
774.6SAP

Properties (5)

additional_info
RFIR
custom_field_three
PROJECTING AGGREGATE THROUGHOUT
custom_field_two
3
customer
LACSD
datetime
2018-05-04T09:36:34-07:00