Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2018, 09:15 AM
  • Section#9_18 0852_18 0851__5102018__I0006.mp4

Date
05/10/2018
W/O
0701110
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14707
Time
2:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0006
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Capital Improvement Program Assesment
Project
20180504MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
18 0852
Downstream MH
18 0851
Dir. of Survey
Downstream
Length Surveyed
734.9 ft.
Total Length
734.9 ft.
Structural Index
3
Structural Quick
524y
Structural Rating
1889
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1889
Pipe schematic from manhole 18 0852 to 18 0851
MH: 18 0852MH: 18 0851downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:35AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR POSSIBLE2 ft. MGO - General Observation - MAG COAT 60% START 9:00 TO 3:002 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR POSSIBLE2 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG29.3 ft. MGO - General Observation - MAG COAT 30% START36.9 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC54.3 ft. MGO - General Observation - MAG G COAT 70% START366 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE613.3 ft. MGO - General Observation - MAG COAT 60% START734.2 ft. SAM - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG734.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE734.2 ft. SAM - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG734.2 ft. MGO - General Observation - MAG COAT 60% FINISH734.2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG VERY SPORATIC734.9 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (10)

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR POSSIBLE

    2 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR POSSIBLE

  • General Observation - MAG COAT 60% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 60% START 9:00 TO 3:00

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR POSSIBLE

    2 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR POSSIBLE

  • Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 30% START

    29.3 ft. - General Observation - MAG COAT 30% START

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    36.9 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    366 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 60% START

    613.3 ft. - General Observation - MAG COAT 60% START

Observations (20)

DistanceCodeObservation
2SSSBLISTERING PEELING CONCRETE
36.9SAPSEVERE AGG SPORATIC
2SRVCIRCUM REBAR POSSIBLE
0AMH2:35AM
2MGOMAG COAT 60% START 9:00 TO 3:00
0MWL
2SRVCIRCUM REBAR POSSIBLE
0MWM
29.3MGOMAG COAT 30% START
734.2SAMSEVERE AGG
54.3MGOMAG G COAT 70% START
613.3MGOMAG COAT 60% START
2SAMSEVERE AGG
734.9AMH3:35AM
2SAMSEVERE AGG
734.2SSSBLISTERING PEELING CONCRETE
734.2SAMSEVERE AGG
734.2MGOMAG COAT 60% FINISH
366SSSBLISTERING PEELING CONCRETE
734.2SAPSEVERE AGG VERY SPORATIC

Properties (4)

custom_field_three
SEVERE AGG MISSING
custom_field_two
3
customer
LACSD
datetime
2018-05-10T02:15:03-07:00