- Date
- 05/11/2016
- W/O
- 568765
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00474
- PipeID
- P06901
- Time
- 3:46 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3373
- Sewer Name
- 05 LOMITA TRUNK RELOCATION
- City
- LOMITA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- RFIR_WO_568765_TV05183_MAY2016
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 27 in.
- Upstream MH
- 05 1688
- Downstream MH
- 05 1674
- Dir. of Survey
- Downstream
- Length Surveyed
- 238.1 ft.
- Total Length
- 238.1 ft.
- Structural Index
- 3
- Structural Quick
- 3321
- Structural Rating
- 11
- O&M Index
- 3
- O&M Quick
- 3100
- O&M Rating
- 3
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole 05 1688 to 05 1674 Observation photos (5)

4.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

9.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

19.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

232.6 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: NO

238.1 ft. - Survey Abandoned - DOWN LEG OF THE U/S SIPHON