Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2018, 10:21 AM
  • 22 0488_22 0487 _20042018_033952.mp4

Date
04/20/2018
W/O
695663
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00800
PipeID
P16827
Time
3:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5574
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_695663_TV22135_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
10 in.
Width
10 in.
Upstream MH
22 0488
Downstream MH
22 0487
Dir. of Survey
Downstream
Length Surveyed
338.8 ft.
Total Length
338.8 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 22 0488 to 22 0487
MH: 22 0488MH: 22 0487downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04880 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start22.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES35.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"38.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"70.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES87.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"90.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"138.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"141.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"151.8 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start161.4 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish170.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start176.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish187.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"189.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"239.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"241.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"289.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"292.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"333.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES337 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish338.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0487

Observation photos (6)

  • Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    22.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    70.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    151.8 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    170.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    333.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
87.1TFC
138.5TFC
189.9TFC
90.1TFC
70.7CL
292.5TFA
141.4TFC
289.8TFC
241.8TFC
161.4CH2
187.1TFC
2SAP
170.7CL
337SAP
0AMH22 0488
239.1TFC
22.7CM
338.8AMH22 0487
38.8TFC
0MWM
151.8CH2
333.7CM
0MWL
176.8CL
35.6TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC358533
custom_field_two
2
customer
LACSD
datetime
2018-04-20T03:21:12-07:00