Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2017, 03:44 PM
  • C 0315_C 0314_6222017_085033.mp4

Date
06/22/2017
W/O
0630229
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00135
PipeID
P09778
Time
8:44 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7441
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20170621MI_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0315
Downstream MH
C 0314
Dir. of Survey
Downstream
Length Surveyed
316 ft.
Total Length
316 ft.
Structural Index
2
Structural Quick
5132
Structural Rating
17
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole C 0315 to C 0314
MH: C 0315MH: C 0314downstream0 ft. AMH - Upstream Manhole, Survey Begins - 09:00 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES AT MH > 508 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start10.6 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: NO35.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.7 ft. MGO - General Observation - ROACHES THROUGHHOUT THE REACH52.2 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"55.4 ft. MGO - General Observation - POSSIBLE MAG COAT, FROM 8 TO 4 OCLOCK, 50%, THROUGHOUT THE REACH63.4 ft. MGP - General Photograph - EXPOSED REBAR VISIBLE THROUGHOUT THE REACH103 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH, FROM 5 TO 7 OCLOCK, 5 %107.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.7 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES157.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES158.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"181 ft. MGP - General Photograph - EXPOSED AGGREGATE VISIBLE221.9 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES247 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES302.6 ft. MGP - General Photograph - EXPOSED REBAR VISIBLE.315.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6" - GREASE DEPOSITS AROUND CONNECTION315.8 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES315.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish315.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316 ft. MSA - Survey Abandoned - DUE TO GREASE DEPOSITS, FROM 8 TO 4 OCLOCK, 20%

Observation photos (14)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    10.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    35.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES THROUGHHOUT THE REACH

    47.7 ft. - General Observation - ROACHES THROUGHHOUT THE REACH

  • General Observation - POSSIBLE MAG COAT, FROM 8 TO 4 OCLOCK, 50%, THROUGHOUT THE REACH

    55.4 ft. - General Observation - POSSIBLE MAG COAT, FROM 8 TO 4 OCLOCK, 50%, THROUGHOUT THE REACH

  • General Photograph - EXPOSED REBAR VISIBLE THROUGHOUT THE REACH

    63.4 ft. - General Photograph - EXPOSED REBAR VISIBLE THROUGHOUT THE REACH

  • General Observation - SLIGHT GREASE THROUGHOUT THE REACH, FROM 5 TO 7 OCLOCK, 5 %

    103 ft. - General Observation - SLIGHT GREASE THROUGHOUT THE REACH, FROM 5 TO 7 OCLOCK, 5 %

  • General Photograph - EXPOSED AGGREGATE VISIBLE

    181 ft. - General Photograph - EXPOSED AGGREGATE VISIBLE

  • Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

    247 ft. - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - EXPOSED REBAR VISIBLE.

    302.6 ft. - General Photograph - EXPOSED REBAR VISIBLE.

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6" - GREASE DEPOSITS AROUND CONNECTION

    315.8 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6" - GREASE DEPOSITS AROUND CONNECTION

  • Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    315.8 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Survey Abandoned - DUE TO GREASE DEPOSITS, FROM 8 TO 4 OCLOCK, 20%

    316 ft. - Survey Abandoned - DUE TO GREASE DEPOSITS, FROM 8 TO 4 OCLOCK, 20%

Observations (29)

DistanceCodeObservation
157.1CM
8SAV
302.6MGPEXPOSED REBAR VISIBLE.
52.2TBA
221.9CC
55.4MGOPOSSIBLE MAG COAT, FROM 8 TO 4 OCLOCK, 50%, THROUGHOUT THE REACH
0AMH09:00 AM
10.6DAGS
10.6CC
315.8TFAGREASE DEPOSITS AROUND CONNECTION
315.8DAGS
315.9SRV
0MWM
8SSS
316MSADUE TO GREASE DEPOSITS, FROM 8 TO 4 OCLOCK, 20%
181MGPEXPOSED AGGREGATE VISIBLE
103MGOSLIGHT GREASE THROUGHOUT THE REACH, FROM 5 TO 7 OCLOCK, 5 %
107.7TFA
0MWL
247CC
315.9SSS
0MGOROACHES AT MH > 50
315.9DAGS
137.7CC
35.8SRV
315.9SAV
63.4MGPEXPOSED REBAR VISIBLE THROUGHOUT THE REACH
47.7MGOROACHES THROUGHHOUT THE REACH
158.4TFA

Properties (3)

custom_field_two
2
customer
LACSD
datetime