Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2017, 03:40 PM
  • C 0313A_C 0313_6212017_100028.mp4

Date
06/21/2017
W/O
0630229
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00135
PipeID
P09776
Time
8:40 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7440
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20170621MI_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0313A
Downstream MH
C 0313
Dir. of Survey
Downstream
Length Surveyed
367.9 ft.
Total Length
367.9 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole C 0313A to C 0313
MH: C 0313AMH: C 0313downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:00 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 OCLOCK, ACTIVE12 ft. MGO - General Observation - MAG COAT FROM 8 TO 4 OCLOCK, 25 %12 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start90.9 ft. MGP - General Photograph - EXPOSED AGGREGATE VISIBLE91.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start186.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"253 ft. MGP - General Photograph - MAG COAT, 8 TO 4 OCLOCK, 25%366.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish366.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367.9 ft. AMH - Downstream Manhole, Survey Ends - 10:20 AM

Observation photos (7)

  • General Observation - MAG COAT FROM 8 TO 4 OCLOCK, 25 %

    12 ft. - General Observation - MAG COAT FROM 8 TO 4 OCLOCK, 25 %

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    52.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - EXPOSED AGGREGATE VISIBLE

    90.9 ft. - General Photograph - EXPOSED AGGREGATE VISIBLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    91.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph - MAG COAT, 8 TO 4 OCLOCK, 25%

    253 ft. - General Photograph - MAG COAT, 8 TO 4 OCLOCK, 25%

  • Downstream Manhole, Survey Ends - 10:20 AM

    367.9 ft. - Downstream Manhole, Survey Ends - 10:20 AM

Observations (17)

DistanceCodeObservation
12MGOMAG COAT FROM 8 TO 4 OCLOCK, 25 %
12SSS
0AMH10:00 AM
366.2DAGS
366.2SSS
367.9AMH10:20 AM
366.2SRV
253MGPMAG COAT, 8 TO 4 OCLOCK, 25%
0MWM
90.9MGPEXPOSED AGGREGATE VISIBLE
0MWL
12SAV
52.1SRV
0MGOCONNECTION AT MH, 9 OCLOCK, ACTIVE
91.3DAGS
186.3TFA
366.2SAV

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2017-06-21T08:40:35-07:00