Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2017, 07:15 PM
  • 19 0311_19 0310_6202017_122208.mp4

Date
06/20/2017
W/O
0630229
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00135
PipeID
P09771
Time
12:15 PM
Certificate
415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7438
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20170616DF_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
19 0310
Downstream MH
19 0311
Dir. of Survey
Upstream
Length Surveyed
889 ft.
Total Length
889 ft.
Structural Index
3
Structural Quick
5133
Structural Rating
16
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 19 0310 to 19 0311
MH: 19 0310MH: 19 0311upstream0 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 1:40 PM1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 55% MAG COAT1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1 ft. SZ - Surface Other, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - 20% MAG COAT2.1 ft. MGP - General Photograph5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.1 ft. MGP - General Photograph143.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open201.3 ft. MGP - General Photograph293.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open294 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 11 to 05 o'clock, , within 8 inches of joint: YES411.3 ft. MGP - General Photograph448.9 ft. MGP - General Photograph - SPALLING457.4 ft. MGP - General Photograph - AGGREGATE551.8 ft. MGP - General Photograph561.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open565.3 ft. MGP - General Photograph - PEELING/FLAKING582.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG COAT656.3 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% MAG COAT656.3 ft. SZ - Surface Other, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - 20 % MAG COAT665.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start710.9 ft. MGP - General Photograph - AGGREGATE/SPALLING/GREASE756.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open795.1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG COAT795.2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 75% MAG COAT851.9 ft. MGP - General Photograph887 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start887 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start887 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG COAT887 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start889 ft. MWL - Water Level, 30 %of cross sectional area889 ft. MWM - Water Mark, 35 %of cross sectional area889 ft. AMH - Downstream Manhole, Survey Begins - 12:18 PM

Observation photos (18)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    37.1 ft. - General Photograph

  • General Photograph - AGGREGATE/SPALLING/GREASE

    178.1 ft. - General Photograph - AGGREGATE/SPALLING/GREASE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    223.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - 20 % MAG COAT

    232.7 ft. - Surface Other, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - 20 % MAG COAT

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG COAT

    306.6 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG COAT

  • General Photograph - PEELING/FLAKING

    323.7 ft. - General Photograph - PEELING/FLAKING

  • General Photograph

    337.2 ft. - General Photograph

  • General Photograph - AGGREGATE

    431.6 ft. - General Photograph - AGGREGATE

  • General Photograph - SPALLING

    440.1 ft. - General Photograph - SPALLING

  • General Photograph

    477.7 ft. - General Photograph

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 11 to 05 o'clock,  , within 8 inches of joint: YES

    595 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 11 to 05 o'clock, , within 8 inches of joint: YES

  • General Photograph

    687.7 ft. - General Photograph

  • General Photograph

    881.9 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    884 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    886.9 ft. - General Photograph

Observations (37)

DistanceCodeObservation
440.1MGPSPALLING
323.7MGPPEELING/FLAKING
223.2SAP
889SRV
888SAV
2SAV
477.7MGP
306.6SZ55% MAG COAT
888SAP
889AMH1:40 PM
431.6MGPAGGREGATE
232.7SZ50% MAG COAT
884SRV
327.9TBOpen
2SSS
687.7MGP
595.1TBOpen
2SZ75% MAG COAT
0MWL
37.1MGP
888SSS
888SZ55% MAG COAT
888CM
745.6TBOpen
881.9MGP
132.6TBOpen
0MWM
93.9SZ50% MAG COAT
2CM
232.7SZ20 % MAG COAT
595DAE
337.2MGP
93.8SZ75% MAG COAT
178.1MGPAGGREGATE/SPALLING/GREASE
886.9MGP
888SZ20% MAG COAT
0AMH12:18 PM

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2017-06-20T12:15:50-07:00