Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 16, 2017, 08:18 PM
  • C 0310_C 0309_6162017_132731.mp4

Date
06/16/2017
W/O
0630229
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00135
PipeID
P09770
Time
1:18 PM
Certificate
415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7438
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20170616DF_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
C 0310
Downstream MH
C 0309
Dir. of Survey
Downstream
Length Surveyed
287.5 ft.
Total Length
287.5 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole C 0310 to C 0309
MH: C 0310MH: C 0309downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:21 PM2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG COAT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.9 ft. MGP - General Photograph - SPALLING/AGGREGATE45.6 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 40% MAG COAT45.6 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 75% MAG COAT56.2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start91.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start128.1 ft. MGP - General Photograph159.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open209.2 ft. MGP - General Photograph - AGGREGATE262.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES286.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"286.5 ft. MGP - General Photograph - PROTRUDING CONN 1 TO 4 O'CLOCK 1"286.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES287.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.5 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% MAG COAT287.5 ft. MSA - Survey Abandoned - PROTRUDING CONN 1 TO 4 O'CLOCK 1"287.5 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish287.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (11)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG COAT

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - SPALLING/AGGREGATE

    32.9 ft. - General Photograph - SPALLING/AGGREGATE

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 40% MAG COAT

    45.6 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 40% MAG COAT

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    56.2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    91.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    128.1 ft. - General Photograph

  • General Photograph - AGGREGATE

    209.2 ft. - General Photograph - AGGREGATE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock,  , within 8 inches of joint: YES

    262.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES

  • General Photograph - PROTRUDING CONN 1 TO 4 O'CLOCK 1"

    286.5 ft. - General Photograph - PROTRUDING CONN 1 TO 4 O'CLOCK 1"

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock,  , within 8 inches of joint: YES

    286.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
286.5TFA
0MGOROACHES @ MH
287.5SAV
2SZ75% MAG COAT
209.2MGPAGGREGATE
0MWL
287.5SZ40% MAG COAT
286.5MGPPROTRUDING CONN 1 TO 4 O'CLOCK 1"
159.2TFOpen
45.6SZ40% MAG COAT
128.1MGP
91.6SRV
287.5MSAPROTRUDING CONN 1 TO 4 O'CLOCK 1"
32.9MGPSPALLING/AGGREGATE
262.4DAGS
0MWM
56.2SAP
45.6SZ75% MAG COAT
286.5DAGS
287.5SAP
0AMH1:21 PM
287.5SRV
2SAV

Properties (3)

custom_field_two
5
customer
LACSD
datetime
2017-06-16T13:18:38-07:00