Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2018, 09:00 AM
  • A 0248_C 0119A_522018_023213.mp4

Date
05/02/2018
W/O
0694536
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00127
PipeID
P09641
Time
2:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0850
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Routine Assessment
Project
20180502MDM_JOINT_OUTFALL_C_UNIT_4B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
C 0119A
Downstream MH
A 0248
Dir. of Survey
Upstream
Length Surveyed
36.7 ft.
Total Length
36.7 ft.
Structural Index
4
Structural Quick
5441
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole C 0119A to A 0248
MH: C 0119AMH: A 0248upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:45AM STOPLOG IN PLACE0.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR0.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE0.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR0.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR19.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR19.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM BROKEN MISSING21.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR23.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM27.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG27.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGGSPORATIC27.2 ft. MGO - General Observation - 48" RCP34.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE34.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC36.7 ft. MWM - Water Mark, 20 %of cross sectional area36.7 ft. AMH - Downstream Manhole, Survey Begins - 2:00AM36.7 ft. MWL - Water Level, 20 %of cross sectional area - NO FLOW

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    9.5 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    12.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    15.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM BROKEN MISSING

    17 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM BROKEN MISSING

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    17.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Upstream Manhole, Survey Ends - 2:45AM STOPLOG IN PLACE

    36.7 ft. - Upstream Manhole, Survey Ends - 2:45AM STOPLOG IN PLACE

Observations (18)

DistanceCodeObservation
2SSSBLISTERING CONCRETE
17.6SRCCIRCUM REBAR
15.2SRVLONG REBAR
2SAPSEVERE AGG SPORATIC
36SRCCIRCUM REBAR
12.8SRVCIRCUM
0MWM
36SSSBLISTERING CONCRETE
36.7AMH2:45AM STOPLOG IN PLACE
36SRVCIRCUM REBAR
36SAMSEVERE AGG
9.5SAMSEVERE AGG
9.5SAPSEVERE AGGSPORATIC
36SRVLONG REBAR
17SRCCIRCUM BROKEN MISSING
0AMH2:00AM
0MWLNO FLOW
9.5MGO48" RCP

Properties (5)

additional_info
REVERSE INSPECTION
custom_field_three
CIRCUM REBAR CORRODED MISSING
custom_field_two
1
customer
LACSD
datetime
2018-05-02T02:00:00-07:00