Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2016, 07:16 AM
  • 02 0377A_02 0377 _20160809_012839.mp4

Date
08/09/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02693
Time
12:16 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3678
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0377A
Downstream MH
02 0377
Dir. of Survey
Downstream
Length Surveyed
205.8 ft.
Total Length
205.8 ft.
Structural Index
3
Structural Quick
3311
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0377A to 02 0377
MH: 02 0377AMH: 02 0377downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 0377A0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.6 ft. CC - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES13.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"13.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES45 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"85.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"112.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"144.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"163.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"177.4 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES197.2 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES202.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish205.8 ft. MGO - General Observation - STUB 3 O'CLOCK205.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0377

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

    2.6 ft. - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    13.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    177.4 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    197.2 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MWM
112.8TFA
202.8DAGS
85.3TF
13.3TF
197.2CM
205.8MGOSTUB 3 O'CLOCK
205.8AMH02 0377
177.4CM
0MWL
1.8DAGS
2.6CC
163.7TFA
0AMH02 0377A
45TFC
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
144.1TFA
13.3CM

Properties (4)

additional_info
SC306008
custom_field_two
4
customer
LACSD
datetime
2016-08-09T00:16:00-07:00