Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2016, 04:47 AM
  • 02 0398_02 0397 _20160811_230304.mp4

Date
08/11/2016
W/O
252431
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00250
PipeID
P02719
Time
9:47 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3681
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
SOUTH GATE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_252431_TV02049_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0398
Downstream MH
02 0397
Dir. of Survey
Downstream
Length Surveyed
162.8 ft.
Total Length
162.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 0398 to 02 0397
MH: 02 0398MH: 02 0397downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03980 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE7.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start30.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"37.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"81.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"86.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"127.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"132.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"159.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish162.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE162.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0397

Observation photos (4)

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    37.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    132.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

Observations (15)

DistanceCodeObservation
0MWL
30.4TFC
86.5TFA
0AMH02 0398
0MWM
81.3TFC
162.8MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
0MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
132.9TFC
7.2DAGS
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
127.7TFC
37.2TFC
159.3DAGS
162.8AMH02 0397

Properties (4)

additional_info
SC306011
custom_field_two
4
customer
LACSD
datetime
2016-08-11T21:47:35-07:00