Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2018, 07:36 AM
  • 08 0061_08 0060 _12042018_004736.mp4

Date
04/12/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00063
Time
12:36 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5528
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0061
Downstream MH
08 0060
Dir. of Survey
Downstream
Length Surveyed
298.3 ft.
Total Length
298.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 08 0061 to 08 0060
MH: 08 0061MH: 08 0060downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00610 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0.1 ft. MWM - Water Mark, 15 %of cross sectional area4.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK298.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK298.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0060

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
188.7TFC
137.7TF
0AMH08 0061
90.3TFC
298.2CM
0MGOCONNECTION AT MH 3 O'CLOCK
298.3MGOCONNECTION AT MH 3 O'CLOCK
4.3CM
38.8TF
298.3MGOCONNECTION AT MH 9 O'CLOCK
298.3AMH08 0060
0.1MWM
0MWL

Properties (4)

additional_info
SC358735
custom_field_two
3
customer
LACSD
datetime
2018-04-12T00:36:33-07:00