Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2018, 06:33 AM
  • 08 0067_08 0066 _11042018_234327.mp4

Date
04/11/2018
W/O
694025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P00069
Time
11:33 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5528
Sewer Name
08 MAIN STREET TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_694025_TV08116_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0066
Downstream MH
08 0067
Dir. of Survey
Upstream
Length Surveyed
251.8 ft.
Total Length
251.8 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
145
Pipe schematic from manhole 08 0066 to 08 0067
MH: 08 0066MH: 08 0067upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 08 00672 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.5 ft. RFJ - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YES47.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"151 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start244.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.8 ft. MWM - Water Mark, 15 %of cross sectional area251.8 ft. AMH - Downstream Manhole, Survey Begins - 08 0066251.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
249.8CM
204TFC
0MWM
251.8MGOCONNECTION AT MH 9 O'CLOCK
0AMH08 0066
0MWL
251.8AMH08 0067
8.4CM
52.3TFC
151.5TF
245.3RFJ
7.7TFC
100.8TFC

Properties (4)

additional_info
SC358735
custom_field_two
3
customer
LACSD
datetime
2018-04-11T23:33:17-07:00