- Date
- 10/27/2017
- W/O
- 0670769
- Weather
- Dry
- Operator/Surveyor
- REVELES
- Sewer ID
- Z00471
- PipeID
- P06990
- Time
- 12:40 AM
- Certificate
- U-115-06022630
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0662
- Sewer Name
- 05 LOMITA TRUNK
- City
- LOMTA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 32
- Purpose
- Capital Improvement Program Assesment
- Project
- 10272017VMR_LOMITA_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Upstream MH
- 05 1763
- Downstream MH
- 05 1762
- Dir. of Survey
- Downstream
- Length Surveyed
- 262.9 ft.
- Total Length
- 262.9 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 3
- O&M Quick
- 5125
- O&M Rating
- 15
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 15
Pipe schematic from manhole 05 1763 to 05 1762 Observation photos (4)

6 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES, Start

162.7 ft. - Deposits Settled Gravel, 5 %of cross sectional area, at 12 o'clock, , within 8 inches of joint: YES

257.3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 03 o'clock, , within 8 inches of joint: YES

262.9 ft. - Deposits Attached Grease, 50 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES