Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2017, 07:30 AM
  • 02 0313_02 0312_6272017_004108.mp4

Date
06/27/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02627
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0575
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Routine Assessment
Project
20170626MDM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0313
Downstream MH
02 0312
Dir. of Survey
Downstream
Length Surveyed
329.4 ft.
Total Length
329.4 ft.
Structural Index
2
Structural Quick
4134
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 02 0313 to 02 0312
MH: 02 0313MH: 02 0312downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM7 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE8 ft. MGO - General Observation - WHITE BUILD UP ON PIPE14.5 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT24.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped30.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H30.4 ft. MWM - Water Mark, 40 %of cross sectional area34.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H34.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H38.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H38.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL50.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL50.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H59.1 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H62.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SJ62.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - H70.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL79.4 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H79.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H82.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H86.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL86.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H98.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS98.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS98.8 ft. FL - Fracture Longitudinal, at 09 TO 3 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS98.8 ft. FL - Fracture Longitudinal, at 09 TO 3 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS226.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped252.5 ft. MGO - General Observation - 18" VCP322.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped329.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 40% HAIRLINE AT JOINTS329.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active329.4 ft. FL - Fracture Longitudinal, at 09 TO 3 o'clock, within 8 inches of joint: YES, Finish - 20% AT JOINTS329.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT AT JOINTS329.4 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM329.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS

Observation photos (3)

  • General Observation - WHITE BUILD UP ON PIPE

    8 ft. - General Observation - WHITE BUILD UP ON PIPE

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - H

    62.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - H

  • General Observation - 18" VCP

    252.5 ft. - General Observation - 18" VCP

Observations (37)

DistanceCodeObservation
226.6TFCCapped
8MGOWHITE BUILD UP ON PIPE
38.5FCH
329.4FC40% HAIRLINE AT JOINTS
86.4FCSL
30.4FCH
0MWL
322.6TFCCapped
30.4MWM
62.9FLSJ
252.5MGO18" VCP
34.2FCH
98.8FCSLIGHT AT JOINTS
82.5FCH
329.4MGOConn. @ Mh, 9 O' Clock. Active
34.2FCH
98.8FCHAIRLINE AT JOINTS
329.4FL20% AT JOINTS
98.8FLHAIRLINE AT JOINTS
98.8FLSLIGHT AT JOINTS
329.4FC30% SLIGHT AT JOINTS
86.4FCH
50.7FCSL
79.4FCH
50.7FCH
79.4FCH
329.4AMH1:30AM
38.5FLSL
59.1FCH
329.4FL20% SLIGHT AT JOINTS
62.9FMH
7FCHAIRLINE
70.9FCSL
24.2TFCCapped
0MWM
0AMH12:35AM
14.5FCSLIGHT

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-06-27T00:30:00-07:00