Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2018, 06:13 AM
  • 15 1121_15 1120 _29032018_232847.mp4

Date
03/29/2018
W/O
691318
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00615
PipeID
P12881
Time
11:13 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5515
Sewer Name
15 MERCED TRUNK, SECTION 2
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_691318_TV15100_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 1121
Downstream MH
15 1120
Dir. of Survey
Downstream
Length Surveyed
210.1 ft.
Total Length
210.1 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 1121 to 15 1120
MH: 15 1121MH: 15 1120downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 11210 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH18.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"63.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES149 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. AMH - Downstream Manhole, Survey Ends - 15 1120

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    130.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
81.3TF
105TF
0MWL
210.1AMH15 1120
18.6TFC
172.9TF
149TFC
0AMH15 1121
130.4CL
0MWM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
63.4TF
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
119.5TF

Properties (4)

additional_info
SC358721
custom_field_two
3
customer
LACSD
datetime
2018-03-29T23:13:07-07:00