Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2018, 07:29 AM
  • 15 1124_15 1123 _30032018_004531.mp4

Date
03/30/2018
W/O
691318
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00615
PipeID
P12884
Time
12:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5515
Sewer Name
15 MERCED TRUNK, SECTION 2
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_691318_TV15100_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 1123
Downstream MH
15 1124
Dir. of Survey
Upstream
Length Surveyed
327.9 ft.
Total Length
327.9 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 1123 to 15 1124
MH: 15 1123MH: 15 1124upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 112412.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"24.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.4 ft. RFJ - Roots Fine Joint, from 09 to 11 o'clock, within 8 inches of joint: YESR253.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES266.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES308.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"327.9 ft. MWL - Water Level, 15 %of cross sectional area327.9 ft. AMH - Downstream Manhole, Survey Begins - 15 1123327.9 ft. MWM - Water Mark, 40 %of cross sectional area327.9 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (3)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    38.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    74.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 11 o'clock, within 8 inches of joint: YESR

    80.5 ft. - Roots Fine Joint, from 09 to 11 o'clock, within 8 inches of joint: YESR

Observations (18)

DistanceCodeObservation
0MWL
303.8TF
315.4TF
19.4TF
80.5RFJ
207.7TF
213.1TF
0AMH15 1123
327.9AMH15 1124
169TF
145.7TF
199.2TF
38.1CL
74.5CL
61.2TFC
0MWM
88TF
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH

Properties (4)

additional_info
SC358721
custom_field_two
3
customer
LACSD
datetime
2018-03-30T00:29:55-07:00