Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2018, 09:01 AM
  • 15 1118_15 1117 _30032018_021258.mp4

Date
03/30/2018
W/O
691318
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00615
PipeID
P12878
Time
2:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5515
Sewer Name
15 MERCED TRUNK, SECTION 2
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_691318_TV15100_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 1118
Downstream MH
15 1117
Dir. of Survey
Downstream
Length Surveyed
209.4 ft.
Total Length
209.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 1118 to 15 1117
MH: 15 1118MH: 15 1117downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 11180 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"8.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"19.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES205.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"209 ft. MGO - General Observation - GHOUT THE REACH, FROM 03 TO 09 O'CLOCK, 5%209.4 ft. AMH - Downstream Manhole, Survey Ends - 15 1117209.4 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    201.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
209.4AMH15 1117
106.8TF
0AMH15 1118
0MWM
19.1TF
8.5TB
209MGOGHOUT THE REACH, FROM 03 TO 09 O'CLOCK, 5%
124.1TF
0MWL
201.5CM
7.2TF
132.9TB
209.4MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
205.3TF
58.6TF

Properties (4)

additional_info
SC358721
custom_field_two
3
customer
LACSD
datetime
2018-03-30T02:01:02-07:00