Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2017, 05:49 AM
  • 05 1467_05 1466 _20062017_000428.mp4

Date
06/19/2017
W/O
640732
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00438
PipeID
P06689
Time
10:49 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3973
Sewer Name
05 EL NIDO TRUNK
City
TORRANCE CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
WO_640732_TV05300_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1467
Downstream MH
05 1466
Dir. of Survey
Downstream
Length Surveyed
320 ft.
Total Length
320 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
315
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
319
Pipe schematic from manhole 05 1467 to 05 1466
MH: 05 1467MH: 05 1466downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 14672 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start62.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"109.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"156.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"159.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"210.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"257.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"307.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"316 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish317 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish319.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK320 ft. AMH - Downstream Manhole, Survey Ends - 05 1466

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
257.6TFC
2SSS
156.6TFC
2.5SAV
319.3MGOCONNECTION AT THE MH 3 O'CLOCK
317SSS
109.5TFC
0MWL
159.9TFC
0MWM
210.1TFC
307.9TFC
316SAV
0AMH05 1467
62.2TFC
320AMH05 1466

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2017-06-19T22:49:42-07:00