- Date
- 11/07/2017
- W/O
- 0671874
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z01180
- PipeID
- P25025
- Time
- 4:59 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6861
- Sewer Name
- G JOINT OUTFALL G - UNIT 8
- City
- COMPTON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 21
- Purpose
- Routine assessment
- Project
- JOINT_OUTFALL_G_UNIT_8
- Material
- RGRCP-PTL
- Shape
- Circular
- Height
- 48 in.
- Upstream MH
- G 0120
- Downstream MH
- G 0119
- Dir. of Survey
- Downstream
- Length Surveyed
- 195.5 ft.
- Total Length
- 195.5 ft.
- Structural Index
- 3
- Structural Quick
- 3G00
- Structural Rating
- 120
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 125
Pipe schematic from manhole G 0120 to G 0119 Observation photos (3)

2 ft. - Lining Failure Blistered, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SMALL

8 ft. - General Observation - 36" RGRCP-PTL

58.7 ft. - Lining Failure Blistered, from 09 to 03 o'clock, within 8 inches of joint: NO - SMALL