- Date
- 11/07/2017
- W/O
- 0671874
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z01180
- PipeID
- P25026
- Time
- 2:48 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6861
- Sewer Name
- G JOINT OUTFALL G - UNIT 8
- City
- COMPTON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 21
- Purpose
- Routine assessment
- Project
- JOINT_OUTFALL_G_UNIT_8
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- G 0121
- Downstream MH
- G 0120
- Dir. of Survey
- Downstream
- Length Surveyed
- 79.6 ft.
- Total Length
- 79.6 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 5141
- O&M Rating
- 43
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 43
Pipe schematic from manhole G 0121 to G 0120 Observation photos (4)

0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

2 ft. - General Observation - THIN DARK GREASE COAT ON PIPE

8 ft. - General Observation - 36" VCP

58.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES