Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 24, 2018, 07:20 PM
  • D 0087_D 0086_4242018_122703.mp4

Date
04/24/2018
W/O
0696317
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00155
PipeID
P09987
Time
12:20 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7691
Sewer Name
D JOINT OUTFALL D - UNIT 5
City
GARDENA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20180424SHO_JOINT_OUTFALL_D_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
D 0087
Downstream MH
D 0086
Dir. of Survey
Downstream
Length Surveyed
299.5 ft.
Total Length
299.5 ft.
Structural Index
4
Structural Quick
5332
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
23
Pipe schematic from manhole D 0087 to D 0086
MH: D 0087MH: D 0086downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12253 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start12.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start30.5 ft. MGO - General Observation - 15% MAG COAT INTACT43.5 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish99.5 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start175.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start181.7 ft. MGO - General Observation - ODD CONNECTION, 12191.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish208.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES294.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start299.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish299.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish299.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish299.5 ft. AMH - Downstream Manhole, Survey Ends - 1240

Observation photos (7)

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    12.2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    99.5 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    175.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ODD CONNECTION, 12

    181.7 ft. - General Observation - ODD CONNECTION, 12

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    208.9 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    294.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MWL
294.3SRV
208.9SRV
30.5MGO15% MAG COAT INTACT
0MWM
99.5SAV
299.2SRV
191.9SRV
12.2SSS
181.7MGOODD CONNECTION, 12
299.5AMH1240
299.2SSS
0AMH1225
299.2SAV
43.5SAV
175.7SRV
3SAV

Properties (5)

additional_info
RFIR
custom_field_three
VISIBLE REBAR & AGGREGATE
custom_field_two
2
customer
LACSD
datetime
2018-04-24T12:20:46-07:00