Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2018, 09:36 AM
  • 18 1081_18 1080_4232018_024303.mp4

Date
04/23/2018
W/O
0700361
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00675
PipeID
P14941
Time
2:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0835
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
20180413MDM_FLORENCE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 1081
Downstream MH
18 1080
Dir. of Survey
Downstream
Length Surveyed
333.6 ft.
Total Length
333.6 ft.
Structural Index
2
Structural Quick
312E
Structural Rating
67
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
67
Pipe schematic from manhole 18 1081 to 18 1080
MH: 18 1081MH: 18 1080downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:40AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped8 ft. MGO - General Observation - 18" VCP11.4 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL11.4 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SLIGHT52.4 ft. FC - Fracture Circumferential, from 12 to 05 o'clock, within 8 inches of joint: YES - SL62.3 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE62.3 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL67.5 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL67.5 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL77.4 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - SL88 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL92.8 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL107.8 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - SL173.9 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL173.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H173.9 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL179 ft. FC - Fracture Circumferential, from 11 to 05 o'clock, within 8 inches of joint: YES - SL198.7 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL204.6 ft. MGO - General Observation - HEATED FLOW SHUTS OFF CAMERA204.6 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H224.5 ft. FC - Fracture Circumferential, from 07 to 11 o'clock, within 8 inches of joint: YES - SL229.2 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL229.2 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL234.2 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL239.5 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL239.5 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL244.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL244.6 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL249.6 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL254.4 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL259.7 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL264.9 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL290.2 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL294.9 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL294.9 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL325.6 ft. FC - Fracture Circumferential, from 12 to 05 o'clock, within 8 inches of joint: YES - SL333.6 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observations (41)

DistanceCodeObservation
229.2FCSL
62.3FCHAIRLINE
67.5FCSL
204.6MGOHEATED FLOW SHUTS OFF CAMERA
0MWL
0MWM
239.5FCSL
229.2FCSL
62.3FCSL
204.6FCH
179FCSL
239.5FCSL
0AMH2:40AM
234.2FCSL
325.6FCSL
67.5FCSL
294.9FCSL
173.9FCSL
294.9FCSL
290.2FCSL
77.4FCSL
8MGO18" VCP
333.6AMH3:20AM
259.7FCSL
92.8FCSL
264.9FCSL
107.8FCSL
0MGOConn. @ Mh, 9 O' Clock. Active
11.4FCSL
224.5FCSL
244.6FLSL
249.6FCSL
11.4FCSLIGHT
173.9FCH
0MGOConn. @ Mh, 3 O' Clock. Capped
244.6FCSL
88FCSL
254.4FCSL
52.4FCSL
198.7FCSL
173.9FCSL

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime