Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2018, 07:34 AM
  • 18 1082_18 1081_4232018_014749.mp4

Date
04/23/2018
W/O
0700361
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00675
PipeID
P14942
Time
12:34 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0835
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
20180413MDM_FLORENCE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 1082
Downstream MH
18 1081
Dir. of Survey
Downstream
Length Surveyed
358.7 ft.
Total Length
358.7 ft.
Structural Index
2
Structural Quick
312E
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
61
Pipe schematic from manhole 18 1082 to 18 1081
MH: 18 1082MH: 18 1081downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. AMH - Downstream Manhole, Survey Begins - 1:30AM0 ft. MWL - Water Level, 10 %of cross sectional area8 ft. MGO - General Observation - 18" VCP14.7 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SLIGHT14.7 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SLIGHT19.5 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL34.9 ft. FC - Fracture Circumferential, from 07 to 11 o'clock, within 8 inches of joint: YES - SL40.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL40.1 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - HAIRLINE40.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H45 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL45 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL60.1 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES - SL64.7 ft. MWM - Water Mark, 40 %of cross sectional area75.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL76.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL90.7 ft. FC - Fracture Circumferential, from 11 to 05 o'clock, within 8 inches of joint: YES - SL90.7 ft. MGO - General Observation - FLOW HEAT SHUTS OF CAMERA95.3 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL100.7 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL100.7 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL115.9 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - SL115.9 ft. FC - Fracture Circumferential, from 07 to 01 o'clock, within 8 inches of joint: YES - SL121.3 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL121.3 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL126 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H131.8 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL156.4 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - H197.2 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL197.2 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL202.3 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SL283.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL288.5 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL288.5 ft. MGO - General Observation - HEATD FLOW SHUTS DOWN CAMERA288.5 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES326.3 ft. FC - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - SL358.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active358.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped358.7 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (2)

  • General Observation - 18" VCP

    8 ft. - General Observation - 18" VCP

  • Water Mark, 40 %of cross sectional area

    64.7 ft. - Water Mark, 40 %of cross sectional area

Observations (42)

DistanceCodeObservation
100.7FCSL
76.9FCSL
0MGOConn. @ Mh, 9 O' Clock. OPEN
60.1FCSL
40.1FCSL
131.8FCSL
75.6FLSL
45FCSL
45FCSL
0MWM
358.1MGOConn. @ Mh, 9 O' Clock. Active
64.7MWM
34.9FCSL
100.7FCSL
115.9FCSL
40.3FCH
288.5FCSL
8MGO18" VCP
14.7FCSLIGHT
197.2FCSL
90.7FCSL
126FCH
14.7FCSLIGHT
121.3FCSL
288.5MGOHEATD FLOW SHUTS DOWN CAMERA
40.1FCHAIRLINE
90.7MGOFLOW HEAT SHUTS OF CAMERA
283.3FCSL
202.3FCSL
288.5FC
0MGOConn. @ Mh, 3 O' Clock. OPEN
19.5FCSL
358.1MGOConn. @ Mh, 3 O' Clock. Capped
156.4FCH
326.3FCSL
197.2FCSL
0AMH1:30AM
95.3FCSL
0MWL
115.9FCSL
358.7AMH2:30AM
121.3FCSL

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-04-23T00:34:54-07:00