Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2018, 09:36 AM
  • 02 0366A_02 0366_4212018_024937.mp4

Date
04/21/2018
W/O
0701224
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00250
PipeID
P02681
Time
2:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0833
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20180220MDM_DOWNEY_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0366A
Downstream MH
02 0366
Dir. of Survey
Downstream
Length Surveyed
299 ft.
Total Length
299 ft.
Structural Index
2
Structural Quick
4138
Structural Rating
64
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
69
Pipe schematic from manhole 02 0366A to 02 0366
MH: 02 0366AMH: 02 0366downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area7 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE8 ft. MGO - General Observation - 18" VCP10.1 ft. FC - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - SL10.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE14.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL14.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H15.1 ft. DSZ - Deposits Settled Other, 10%of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCK15.1 ft. MGP - General Photograph - VOID SOIL VISIBLE15.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - Active-VOID SOIL VISIBLE22.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped27.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H27.2 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - H27.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H31.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H35.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H39.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H51.3 ft. FL - Fracture Longitudinal, at 07 TO 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS51.3 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS65 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped75.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped77.7 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL81.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL81.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL89.8 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL97.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL102.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL106.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL110.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL111 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open113 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL126.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open126.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL136.3 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS136.3 ft. FL - Fracture Longitudinal, at 07 TO 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS161.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active172.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open212 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active214.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT214.1 ft. FM - Fracture Multiple, from 07 to 06 o'clock, within 8 inches of joint: YES - SLIGHT221.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL227.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped262.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open273.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped298.4 ft. FL - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS298.4 ft. FL - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS298.4 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - 70% SLIGHT AT JOINTS298.4 ft. FC - Fracture Circumferential, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - 60% HAIRLINE AT JOINTS299 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (3)

  • General Photograph - VOID SOIL VISIBLE

    15.1 ft. - General Photograph - VOID SOIL VISIBLE

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 6" - Active-VOID SOIL VISIBLE

    15.1 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - Active-VOID SOIL VISIBLE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    214.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

Observations (52)

DistanceCodeObservation
7FCHAIRLINE
113FCSL
27.2FLH
298.4FL50% HAIRLINE AT JOINTS
15.1DSZROCK
106.3FCSL
15.1MGPVOID SOIL VISIBLE
10.1FCSL
126.7TFOpen
14.1FLSL
0MGOConn. @ Mh, 3 O' Clock. Active
136.3FCSLIGHT AT JOINTS
77.7FCSL
75.8TFCCapped
81.9FCSL
27.2FCH
299AMH3:40AM
14.1FCH
298.4FL20% SLIGHT AT JOINTS
35.3FCH
65TFCCapped
110.1FCSL
227.2TFCCapped
161.7TFActive
10.1FCHAIRLINE
298.4FC70% SLIGHT AT JOINTS
262.3TFOpen
0AMH2:45AM
221.4FLSL
172.9TFOpen
111TFOpen
27.2FLH
8MGO18" VCP
298.4FC60% HAIRLINE AT JOINTS
136.3FLSLIGHT AT JOINTS
273.2TFCCapped
214.1FLSLIGHT
89.8FCSL
51.3FLHAIRLINE AT JOINTS
212TFActive
97.9FLSL
0MWM
15.1TBDActive-VOID SOIL VISIBLE
51.3FCHAIRLINE AT JOINTS
214.1FMSLIGHT
39.3FCH
81.9FCSL
0MWL
126.7FLSL
31.5FCH
22.3TFCCapped
102.2FCSL

Properties (4)

custom_field_three
CONN WITH VOID SOIL-LONG SLIGHT JOINT TO JOINT LON
custom_field_two
1
customer
LACSD
datetime
2018-04-21T02:36:40-07:00