Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2017, 08:44 AM
  • 05 0385_05 0384 _13072017_025837.mp4

Date
07/13/2017
W/O
640682
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00432
PipeID
P05597
Time
1:44 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3987-SC345551
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
INGLEWOOD CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_640682_TV05179_JUN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
05 0385
Downstream MH
05 0384
Dir. of Survey
Downstream
Length Surveyed
395.5 ft.
Total Length
395.5 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
234
O&M Index
2
O&M Quick
412O
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
394
Pipe schematic from manhole 05 0385 to 05 0384
MH: 05 0385MH: 05 0384downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03850 ft. MWL - Water Level, 25 %of cross sectional area3.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start101 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"273.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"393.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish393.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish395.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0384

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
3.6SAP
273.6TB
395.5AMH05 0384
393.3DAGS
101TB
0MWM
0AMH05 0385
0MWL
3.6DAGS
393.3SAP

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-07-13T01:44:44-07:00